Classic Slimline FF - Installation & Servicing
INSTALLATION
Pack B Contents
z Duct cutting support, 2 off
(cardboard )
z Terminal wall plate, 1 off.
z Terminal grille assy., 1 off.
z Polyurethane foam seal 400
lg., 1 off.
z No. 8 x 8 lg. Pozi pan hd.
screws, 3 off.
7
UNPACKING
Pack A Contents
z The complete boiler
z Installation & Servicing
Instructions
z User's Instructions
z Hardware Pack (listed below)
z Wall mounting template
z Wall mounting plate
z Side outlet terminal mounting
plate
z Flue extension tube - 1 off
z Boiler sealing ring - 1 off
z Flue elbow (for side outlet only)
Cl 1724
Hardware Pack Contents
z 50mm x No. 14 wood screw, 4 off
z 50mm x No. 10 wood screw, 8 off
z Wall plug, 12 off
z Data badge indicator arrow, 1 off
z M8 washer, 1 off
z M5 wing nut, 3 off
z Sealing plate, 1 off
z M8 x 12 Hx. Hd. screw, 1 off
The boiler is supplied fully assembled in Pack A, together with a
standard flue assembly for lengths up to 600mm (23
1/2"), rear or
side flue outlet, in Pack B.
Safety valve setting 3.0 bar
Vessel charge and 0.5 1.0 1.5
initial system pressure bar bar bar
Total water content of system
Expansion vessel volume (litres)
25 litres 2.1 2.7 3.9
50 4.2 5.4 7.8
75 6.3 8.2 11.7
100 8.3 10.9 15.6
125 10.4 13.6 19.5
150 12.5 16.3 23.4
175 14.6 19.1 27.3
200 16.7 21.8 31.2
225 18.7 24.5 35.1
250 20.8 27.2 39.0
275 22.9 30.0 42.9
300 25.0 32.7 46.8
Multiplying factors for
other system volumes 0.0833 0.109 0.156
6
SEALED SYSTEM REQUIREMENTScontinued
Sizing procedure for expansion vessels:
The volume of the expansion vessel (litres)
fitted to a sealed system shall not be less than
that given by the table opposite, multiplied by a
factor of 0.8 (for flow temperature of less than
88°C).
If the system volume exceeds the figure given
in the opposite table for an 8-litre expansion
vessel then an additional vessel may be fitted,
provided that it is as close to the appliance on
the return to the boiler as is practically
possible.
Refer to BS 5449 and BS 7074:1 for detail of
expansion vessel application, selection and
installation.
Optional extra, if ordered (Extension Duct Kit D) is available in a
separate box.
Unpack and check the contents.
INSTALLATION