20
IDS 805 Installer Manual 700-266-02H Issued September 2009
LOCATION 16 Siren Toot on Arm & Disarm
0 Default
1
2
3
Enabled
Disabled
This option allows the user to confirm that arming has occurred. The siren will give a short beep after
successful arming, and two short beeps after disarming. This is recommended if a remote control or
external key-switch is used.
NOTE:
The siren will not beep if the panel is stay armed into or disarmed from the stay mode.
LOCATION 17 Siren Time Out Period
0 0.25 seconds 8 4 minutes
1 10 seconds 9 5 minutes
3 30 seconds 11 15 minutes
4 45 seconds 12 18 minutes
6 2 minutes (Default) 14 21 minutes
7 3 minutes 15 21 minutes
The siren time out period is the period of time for which the siren will sound after an alarm condition is
registered. Select the appropriate time-out period from the table above.
LOCATION 18 Exit Delay Period
0 0.25 seconds 8 4 minutes
1 10 seconds 9 5 minutes
2 20 seconds 10 10 minutes
3 30 seconds (Default) 11 15 minutes
4 45 seconds 12 18 minutes
5 1 minute 13 21 minutes
6 2 minutes 14 21 minutes
7 3 minutes 15 21 minutes
This is the period of time allowed for exiting before the panel arms. The exit delay begins after entry of a
valid user code. During this period, it is possible to violate Entry/Exit and Follower zones without causing
an alarm condition. Select the appropriate exit delay period from the table above.