IDS 805 Installer Manual 700-266-02H Issued September 2009
NOTES ON CONTACT ID
If the panel has been programmed to use the Contact ID reporting format (i.e. location 47=6) it is not
necessary to program the reporting codes. All codes will be reported by default. Table 8 contains a list of
standard (default) Contact ID reporting codes. Under certain conditions, it may be necessary to change
or disable certain codes. If a particular reporting code is not required, program a [0]
(not “10”) into the
relevant locations.
Any event that relates to a specific zone, or to a specific user, will have the relevant zone/user number
attached to the end of the Contact ID reporting code.
If dual reporting is enabled and the Contact ID reporting format is required, both the primary and
secondary communicator formats need to be programmed as Contact ID. It is not possible to use
Contact ID in conjunction with a second format e.g. Domestic Reporting, as the second format will
transmit all codes as FF or F.
It is common not to report stay arming, away arming, and disarming for domestic alarms. To disable the
reporting of these functions, program the following locations:
Arming or Closing code Location 108 = 0
Disarming or Open code Location 109 = 0
Home or Stay arming Location 110 = 0
Table 8: Standard Contact ID Reporting Codes
Description
Codes
Description
Codes
Close by user 3401 Zone bypass 1570
Close by auto arm 3403 Zone shutdown 1573
Close by download 3407 Zone restoral 3130
Close with key-switch 3409 Tamper by zone 1137
Open by user 1401 Keypad tamper 1137
Open by download 1407 Keypad lockout 1137
Open with key-switch 1409 Panic zone 1120
Cancel 1406 Panic 1120
Burglary violation 1130 Keypad panic 1120
Perimeter violation 1131 AC fail 1301
Interior violation 1132 AC restoral 3301
24 Hour (Safe) violation 1133 Low battery 1302
Entry/exit violation 1134 Test report 1602
Day/night violation 1135 Keypad fire 1110
Outdoor violation 1136 Fire 1110
Tamper violation 1137 Duress 1121
Near alarm violation
1138
Keypad medical
1100
Box tamper 1144
The generic Contact ID reporting code for an alarm caused by a zone violation is 1130, corresponding to
a "BURGLARY" description. If you wish particular zone violations to be reported with a description other
than BURGLARY an option may be chosen from Table 9 overleaf. The first digit
of the reporting code
relevant to that zone must be changed to the value as indicated in the table.

Other manuals for IDS 805

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDS 805 and is the answer not in the manual?

IDS 805 Specifications

General IconGeneral
Zones8
ModelIDS 805
BacklightYes
Voltage12V DC
Current50mA
DisplayLED
Operating Temperature-10°C to +50°C