above 11.9V for the panel to register a restoral.
LOCATIONS 132-133 Box Tamper Reporting Code
The box tamper reporting code will be reported if there are open circuit box tamper contacts for more
than 200ms.
LOCATIONS 134-135 Reserved
LOCATIONS 136-139 Installer ID Code (Default = 9999)
The installer’s ID code is used by the installer to enter the program mode. This may be changed by
entering a new 4-digit code into these 4 locations.
Although not possible from the keypad, it is possible using the IDS PC download software to enter an
installers ID code containing the hexadecimal digits A-F. If these digits are used as part of the installers
ID, it will prevent access to programming mode from the keypad. In this case, program access can only
be achieved by using the IDS PC download software.
LOCATION 140 Swinger Shutdown Count Value (Default = 0)
Determines the number of times a zone may be violated during an arm cycle before it is automatically
bypassed. The count will be twice the value entered. The maximum value of 15 may be entered,
corresponding to 30 violations required to force the zone to bypass. Disable swinger shutdown by
entering [0]
in this location.
LOCATION 141 Zone Loop Response
The zone loop response is the period of time for which the zone must be violated before a violation is
registered. A value of [0]
provides a loop response time of 100ms.
LOCATION 142 Zone Trip Count (Default = 0)
This feature is to prevent false alarms while the panel is armed. If the panel is armed and a Follower zone
is violated the number of times programmed into this location within the time period programmed into