LOCATION 156 Secondary Communicator Format (Default = 0)
This communicator format is used if the panel is communicating to two base stations and will be
transmitted to the secondary phone number. See Location 47 and the subsequent notes for information
regarding the programming of this location.
Communication Delay (Default = 0)
If an event occurs that will be reported, the panel will wait for this period of time before transmitting the
relevant reporting codes either by phone or radio outputs. If a valid user code is entered during the delay
period, the reporting codes will not be transmitted. The event will still be recorded in the event log. The
value of this location ranges from 0 to 75 seconds in 5 second increments. Program a value from [0]
to
[15].
Multiply the value of the entry by 5 seconds to calculate the delay time.
The communication of the following events will not be delayed under any circumstances:
Duress
Audible/ Silent Priority Zones
Keypad Panic
Keypad Medical
Keypad Fire
Zone Programmable Outputs (see Loc. 158 - 165)
Programmable Output Controls - Zones
SEE LOCATIONS 22 - 44 and TABLE 6
158 Zone 1 output 0 Disabled
159 Zone 2 output 0 Disabled
160 Zone 3 output 0 Disabled
161 Zone 4 output 0 Disabled
162 Zone 5 output 0 Disabled
163 Zone 6 output 0 Disabled
164 Zone 7 output 0 Disabled
165 Zone 8 output 0 Disabled
A programmable output will be activated when a zone is violated.
LOCATION 166 Low Battery Restoral Prog. O/P (Default = 0)
This output will be triggered once the battery voltage has been restored i.e. the voltage risen to above
11.9V.
LOCATION 167 TLM Fail Programmable Output (Default = 0)
This output will be triggered if telephone line monitoring is enabled, and the line voltage drops below 9V
for more than 30-60 seconds.
TLM Restore programmable Output (Default = 0)
This output will be triggered once telephone line monitoring has been restored to 9V for longer than 30-60
seconds.