EasyManuals Logo

IEC E055-71520301 User Manual

IEC E055-71520301
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
Advanced Setup
On / Off
1 / 2
2 / 4
1 - 5
On / Off
1 - 6
0 - 6
On / Off
F / C
On / Off
NO / NC
Unoccupied /
Off
35 - 99 , OF
OF, 35 - 99
Display Blanking
Single or Dual Setpoint
2-or 4-Pipe System
2-Pipe System Operation
Fan Auto Operation
Deadband/Temp. Swing
1st Stage
Minimum Heat/Cool
Differential
Thermoglow Backlight
Fahrenheit or Celsius
Read Only Remote
Sensor?
Dry Contact Polarity
Dry Contact Operation
Unocc. Cool Setpoint
Unocc. Heat Setpoint
Step
#
Description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Advanced Setup Table
Range
Factory
Default
On
2
4
1
Off
2
2
Off
F
Off
NO
Unoccupied
85
55
Page 15
About Advanced Features & Operation
Page 17
The above figure assumes the minimum on time for the
prior stage has been met to allow the next stage to turn
on, once the deadbands have been exceeded.
TEMPERATURE
DECREASE
INCREASE
Cool
SP
Heat
SP
Med-
speed
fan
Med-
speed
fan
Heating
Cooling
Lo-
speed
fan
Hi-
speed
fan
Lo-
speed
fan
Hi-
speed
fan
DEADBAND OPERATION - Controls one Heat and
one Cool stage with a three speed fan (see below).
The medium speed fan for heat or cool is turned on
when: The temperature spread from the setpoint is
equal to or greater than: the setpoint plus the 1st stage
deadband (step #6, page 12), plus the 2nd stage dead-
band. This 2nd stage deadband is fixed at one degree
and is not adjustable.
The low speed fan for heat or cool is turned on when:
The temperature spread from the setpoint is equal to
or greater than: the setpoint plus the 1st stage dead-
band (step #6, page 12). This 1st stage deadband is
adjustable from 1-6 degrees and the default is two
degrees.
The high speed fan for heat or cool is turned on when:
The temperature spread from the setpoint is equal to or
greater than: the setpoint plus the 1st stage deadband
(step #6, page 12), plus the 2nd stage deadband, plus
the 3rd stage deadband. This 3rd stage deadband is
fixed at one degree and is not adjustable.
DB 3
1
DB 2
1
DB 1
1-6
DB 1
1-6
DB 2
1
DB 3
1

Other manuals for IEC E055-71520301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IEC E055-71520301 and is the answer not in the manual?

IEC E055-71520301 Specifications

General IconGeneral
BrandIEC
ModelE055-71520301
CategoryThermostat
LanguageEnglish

Related product manuals