Increase or reduce the set temperature value according to the system application
(heating/air-conditioning system)
Put switch onto ON position
Make sure the switch is on position (heating system) or o position (air conditioning system)
Problem
The ambienttemperature doesnot correspond tothe temperatureset on thethermostat
Possible cause
Incorrect positioning of the thermostat within the room
Air draughts coming from the electrical wires conduit
Solution
Follow the instructions of paragraph “Placement of the thermostat”
Seal the conduit to prevent warm or cold air draughts