28
23
11. SPECIAL FUNCTIONS.
By pressing the button, a list of options is accessed that
allows to customise functioning of the CAR
V2
remote control,
according to the specic necessities.
To scroll the list, press the + / - buttons and press the
button to select the desired function.
11.1 LANG (language selection).
Allows to set the functioning language of the CAR
V2
remote
control. It is possible to select from Italian (ITA as per standard)
and English (ENG).
11.2 REGULT (Management of regulation parameter).
Allows to customise the functioning parameters of the
CAR
V2
remote control
.
- CH MIN (central heating ow minimum temperature),
allows to regulate the central heating flow minimum
temperature value. Moreover, this value is used to calculate
the curves used for the external probe. Values that are too
high can cause ow temperatures that are too high on average
for room central heating.
- OFFSET (regulation constant), constant that can be regulated
from -15°C to +15°C and which in the presence of the
external probe (optional) modies the set ow temperature
(see Fig. 23)
set as per standard at 0°C.
TM-MAX/MIN = Selected ow temp. range.
Te = External temperature.
EXTERNAL PROBE
FLOW TEMPERATURE CORRECTION LAWS.
EXTERNAL TEMPERATURE FUNCTION AND THE POSITION OF
THE USER TEMP. ADJUSTMENT CENTRAL HEATING.
N.B.: if the self-learning function is enabled, the Oset value
could be modied automatically.
Position of the central heating tem-
perature user adjustment central heat-
ing temp.