ERROR 37
Low power supply voltage.
37
e boiler power supply voltage exceeds 190 VDC.
No
Restore the correct electric power of the appliance (230 VDC ±10%).
Yes
e electric power supply connection wires and relative external
fuses are integral.
No
Restore the electric connection/replace the cables/external fuses.
Yes
Replace the P.C.B.
ERROR 38
Loss of ame signal.
38
It is displayed every time the P.C.B., with the burner on, loses the ame signal.
If normal conditions are restored, the boiler starts to run correctly again without having to be reset.
If the error re-occurs 6 times in 8.5 minutes, the P.C.B. will display error 43 "Loss of continuous ame block".
Make sure the detection electrode is working correctly.
ERROR 43
Block due to loss of continuous ame signal.
43
is will be displayed if error 38 occurs 6 times in 8.5 minutes.
To eliminate the block, the Reset button (5) must be pressed.
See Error 38.