28.2 VICTRIX PRO V2 60 EU COMBUSTION FEATURES
Gas ow rates refer to net caloric value at a temperature of 15°C and at a pressure of 1013 mbar.
Flue gas temperature values refer to an air inlet temperature of 15°C and ow/return temperature of 80/60°C.
Methane (G20) LPG (G31)
Maximum heat input of gas G20 m
3
/h 6.34
Min. heat input of gas G20 m
3
/h 0.83
Maximum heat input of gas G31 kg/h 4.65
Min. heat input of gas G31 kg/h 0.61
Supply pressure mbar 20 37
Flue ow rate at maximum nominal heat output kg/h 96 97
Flue ow rate at maximum nominal heat output
gas 20% H2NG
kg/h 100
Flue ow rate at min heat output kg/h 13 13
Flue ow rate at min heat output
gas 20% H2NG
kg/h 14
Chimney losses with burner on (100% Pn) (80/60°C) % (W) 2,2 (1318)
Chimney losses with burner o % (W) 0,02 (10)
Casing losses with burner on (100% Pn) (80/60°C) % (W) 0,1 (60)
Casing losses with burner o % (W) 0,2 (121)
Flue gas temperature Maximum Heat Input °C 71 71
Flue gas temperature Min. Heat Input °C 65 61
CO
2
at Maximum Heat Input % 9.3 10.4
CO
2
at Maximum Heat Input
gas 20% H2NG
% 8.3
CO
2
at Min. Heat Input % 9.0 10.0
CO
2
at Min. Heat Input
gas 20% H2NG
% 7,9
CO at Maximum Heat Input ppm 160 170
CO at Maximum Heat Input
gas 20% H2NG
ppm 90
CO at Min. Heat Input ppm 3 3
CO at Min. Heat Input
gas 20% H2NG
ppm 1
Weighted CO mg/kWh 17 15
NO
x
at the Maximum Heat Input mg/kWh 41 42
NO
x
at Min. Heat Input mg/kWh 38 42
Weighted NO
x
mg/kWh 41 40
NO
x
class - 6 6