VICTRIX PRO V2 180 EU
126
28.8 VICTRIX PRO V2 180 EU COMBUSTION FEATURES
Gas ow rates refer to net caloric value at a temperature of 15°C and at a pressure of 1013 mbar.
Flue gas temperature values refer to an air inlet temperature of 15°C and ow/return temperature of 80/60°C.
Methane (G20) LPG (G31)
Maximum heat input of gas G20 m
3
/h 18.0
Min. heat input of gas G20 m
3
/h 3.67
Maximum heat input of gas G31 kg/h 13.2
Min. heat input of gas G31 kg/h 2.7
Supply pressure mbar 20 37
Flue ow rate at maximum nominal heat output kg/h 277 274
Flue ow rate at maximum nominal heat output
gas 20% H2NG
kg/h 292
Flue ow rate at min heat output kg/h 60 62
Flue ow rate at min heat output
gas 20% H2NG
kg/h 63
Chimney losses with burner on (100% Pn) (80/60°C) % (W) 1,7 (2890)
Chimney losses with burner o % (W) 0,02 (31)
Casing losses with burner on (100% Pn) (80/60°C) % (W) 0,1 (170)
Casing losses with burner o % (W) 0,18 (306)
Flue gas temperature Maximum Heat Input °C 72 71
Flue gas temperature Min. Heat Input °C 60 60
CO
2
at Maximum Heat Input % 9.1 10.5
CO
2
at Maximum Heat Input
gas 20% H2NG
% 8.0
CO
2
at Min. Heat Input % 8.5 9.3
CO
2
at Min. Heat Input
gas 20% H2NG
% 7.5
CO at Maximum Heat Input ppm 210 305
CO at Maximum Heat Input
gas 20% H2NG
ppm 100
CO at Min. Heat Input ppm 10 9
CO at Min. Heat Input
gas 20% H2NG
ppm 4
Weighted CO mg/kWh 25 28
NO
x
at the Maximum Heat Input mg/kWh 70 73
NO
x
at Min. Heat Input mg/kWh 28 22
Weighted NO
x
mg/kWh 42 34
NO
x
class - 6 6