Power the charger up, once the boot up is complete, connect the EVSE tester to
thecharger.
• ChangethemodeontheEVSEtestertoB,the4statuslightsshouldbegintoash.
• Presstheboostbuttononthecharger,theprimaryLEDandstatusLED’swillgoblue.
• ChangethemodeontheEVSEtestertomodeC.Thestatuslightswillgosolidblue
and a voltage should be indicated on the MFT
• CarryouttheLooptestaspertheMFTmanufacturesinstructions.
RCD Testing
IAWGuidanceNote3toBS7671:2018+A2:2022Section2.6.18.
RCDtestscanbecarriedoutatanypointonthecircuite.g.ontheRCDcontactsorvia
theEVSE.
Testing via the EVSE:
Using a multi-function tester (MFT) and a compatible Electric Vehicle Service Equipment
(EVSE) tester as follows:
Connect the MFT to the EVSE tester as per the manufacturers instructions and set to
modeA.
• SettheMFTto6mA.Ifthetesterdoesnotgoto6mAthenthecalculationmethod
should be used for Zs as the in-built RCD-DD protection will trigger and isolate the
powerrelays.
Power the charger up, once the boot up is complete, connect the EVSE tester to
thecharger.
Change the mode on the EVSE tester to mode B, the 4 status lights should begin
toash.
• Presstheboostbuttononthecharger,theprimaryLEDandstatusLED’swillgoblue.
• ChangethemodeontheEVSEtestertomodeC.Thestatuslightswillgosolidblue
andavoltageshouldbeindicatedontheMFT.
• CarryouttheLooptestaspertheMFTmanufacturersinstructions.
30 Indra Smart Range Installation Guide