Page #58 background imageLoading...
Page #58 background image
53
Voltage Range (Line-
Neutral) [V]*(1)
220 V /230V /240V ±%10
Frequency Range [Hz]
*(1)
47-53
Nominal Apparent
Power [kVA]
10
15
20
30
40
60
80
100
120
Nominal Current [A]
15
23
30
45
61
91
121
151
182
Transfer Duration [ms]
0
STATIC BY-PASS LINE @ 1PH OUTPUT UPS’S
Number of Phases
1P+N+PE
-
Voltage Range (Line-
Neutral) [V]*(1)
220 V /230V /240V ±%10
-
Frequency Range [Hz]
*(1)
47-53
-
Nominal Apparent
Power [kVA]
10
15
20
30
40
-
Nominal Current [A]
45
68
91
136
182
-
Transfer Duration [ms]
0
-
BATTERIES
Battery Type
Sealed lead acid, 12 V
Number of Batteries
2x31
Nominal Battery Voltage
[V]
2x372
Stored
energy time
@ nominal
load with
standard
internal
batteries*(2)
7Ah
14m
6m
4,5m
-
-
9 Ah
25m
10m
7m
2,5m
-
PHYSICAL
Dimensions (WxDxH)
(cm)
40 x 77 x 110
52 x 90 x 130
67 x 73 x 160
63 x 100 x 140
85 x 77 x 182
Weight (kg)
102
110
240
242
260
295
330
STANDARDS
Safety
IEC / EN / TSE 62040-1
Performance
IEC / EN / TSE 62040-3
EMC
IEC / EN / TSE 62040-2
Product Certification
CE