EasyManuals Logo
Home>INFOSEC UPS SYSTEM>UPS>E3 PERFORMANCE RT Series

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series User Manual

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 06 17 AA 59 205 05

3.7 Faults reference code
Fault event
Fault
code
Icon
Fault event
Fault
code
Icon
Bus start fail
01
x
Inverter output short
14
Bus over
02
x
Battery voltage too high
27
x
Bus under
03
x
Battery voltage too low
28
Inverter internal soft
start fail
11
x
Over temperature
41
x
Inverter internal
voltage high
12
x
Over load
43
Inverter internal
voltage high
13
x
Charger failure
45
x
3.8 Warning indicators
Warning
Icon (flashing)
Alarm
Low Battery
Sounding every 2 seconds
Overload
Sounding every second
Battery is not
connected
Sounding every 2 seconds
Over Charge
Sounding every 2 seconds
Site wiring fault
Sounding every 2 seconds
EPO enable
Sounding every 2 seconds
Over temperature
Sounding every 2 seconds
Charger failure
Sounding every 2 seconds
Battery fault
Sounding every 2 seconds (At this time,
UPS is off to remind users of
something wrong with battery)
EEPROM error
Sounding every 2 seconds
Battery replacement
Sounding every 2 seconds

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series and is the answer not in the manual?

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series Specifications

General IconGeneral
BrandINFOSEC UPS SYSTEM
ModelE3 PERFORMANCE RT Series
CategoryUPS
LanguageEnglish

Related product manuals