SGNe Troubleshooting Guide Page 10
Revision 1.0; Davidson, May 2009. ©Ingersoll Rand Proprietary Information
SGNe
Troubleshooting Guide
Danger
Please utilize extreme caution when performing work within the compressor cabinet.
When opening the cabinet: be certain to wear appropriate PPE (Personal Protective Equipment),
follow lock out-tag out procedures, and ensure all safety procedures are followed
.
Reset Averaging
This set point is to reset the time period that the energy status information will be
calculated over. When this set point has been selected and set, the date that is
was last
set will be displayed.
Options
The options screen is similar to the operator set point screen in terms of step
intervals and units. However, the range section allows the operator to turn the
options “ON” or “OFF”. The following are the names and values of each option.
They are viewed by moving up and down with the arrow buttons.
If an option has not been purchased and installed in the unit, the message “Not
Installed” will be shown on the selection display screen. Installation of options
will be done using the IR service tool.
OPTION ITEMS SELECTION MIN. MAX. STEP UNIT Installed
Option
Required
Remote Sensor ON/OFF
--- --- --- ---
No
Sequencer ON/OFF
--- --- --- ---
No
Remote Start/Stop ON/OFF
--- --- --- ---
No
Power Out Restart ON/OFF
--- --- --- ---
Yes
Power Out Restart Time --- 10 600 1 sec Yes
Scheduled Start Day --- Day Day 1 day Yes
Scheduled Start --- 00:00 23:59 1 time Yes
Scheduled Stop Day --- Day Day 1 day Yes
Scheduled Stop
---
00:00 23:59 1 time Yes
Modbus Protocol ON/OFF/ICU
--- --- --- ---
No
Modbus Address --- 1 247 1 --- No