Inovance H0U Series PLC User Manual 
Page 8 of 14 
the terminal is ON and is inactive (state "0") when the terminal is OFF.   
The 250 VAC reinforced insulation must be satisfied between the relay outputs and the 
logic circuit of the PLC. In addition, the 250 VAC reinforced insulation must be satisfied 
between the output terminals of different common terminals. 
Item Relay Output  Transistor Output 
Circuit voltage  250 VAC, 30 VDC below  5–24 VDC 
Circuit insulation  Relay mechanical insulation  Optically coupling insulation   
Action indication  Output contact closing 
Contact closing when optically 
coupling is driven 
Leakage current at open 
circuit 
-  < 0.1 mA/30 VDC 
Minimum load  2 mA/5 VDC  5 mA (5–24 VDC) 
Resistive load 
2 A for a point 
8 A for 4 points in a group sharing 
a common terminal 
8 A for 8 points in a group sharing 
a common terminal 
0.5 A for a point 
0.8 A for 4 points 
1.6 A for 8 points 
Maximu
m 
output 
current 
Inductive load  220 VAC, 80 VA 
High-speed outputs: 7.2 W/24 
VDC 
Others: 12 W/24 VDC 
ON response time  20 ms (max.) 
OFF response time  20 ms (max.) 
High-speed outputs: 10 us 
Others: 0.5 ms 
High-speed output 
frequency 
- 
100 kHz per channel (max.) 
Output common terminal 
Each group shares a common terminal COM. The groups are 
insulated. 
Fuse protection  - 
When some or all transistors in each group are with load, the average current for each channel must not 
exceed 0.2 A. The maximum current for a single channel must not exceed 0.5 A. 
 
Internal Equivalent Circuit 
The following figure shows the internal equivalent circuit of relay output. Output terminals 
are divided into several groups, with each group electrically isolated. The output contacts 
of different groups are connected to different power circuits.
 
efesotomas
on.com