Description of Function Codes
MD280 User Manual
- 122 -
Function Code Parameter Name Setting Range Default
F3-14 Motor switchover delay 0.1–32.0s 0.1s
F3-15 Startup delay after motor switchover 0.1–32.0s 0.2s
F3-14 is used to set the delay from stop of the AC drive to the time of outputting the
contactor control signal.
F3-15 is used to set the delay from the time when the contactor control signal becomes valid
to the time when the AC drive starts up.
Group F4: Start/Stop Control
Function Code Parameter Name Setting Range Default
F4-00 Start mode
0: Direct start
1: Rotational speed tracking restart
0
 0: Direct start
If the DC braking time is set to 0, the AC drive starts to run at the startup
frequency.
If the DC braking time is not 0, the AC drive performs DC braking first and
then starts to run at the startup frequency. It is applicable to small-inertia load
application where the motor is likely to rotate at startup.
 1: Rotational speed tracking restart
7KH$&GULYHMXGJHVWKHURWDWLRQDOVSHHGDQGGLUHFWLRQRIWKHPRWRU¿UVWDQGWKHQVWDUWV
at the tracked frequency. Such smooth start has no impact on the rotating motor. It
is applicable to the restart upon instantaneous power failure of large-inertia load. To
ensure the performance of rotational speed tracking restart, set the motor parameters
in group F1 correctly.
Function Code Parameter Name Setting Range Default
F4-01
Rotational speed
tracking mode
0: From frequency at stop
1: From zero speed
)URPPD[LPXPIUHTXHQF\
0
To complete the rotational speed tracking process within the shortest time, select the proper
mode in which the AC drive tracks the motor rotational speed.
 0: From frequency at stop
It is the commonly selected mode.
 1: From zero frequency
It is applicable to restart after a long time of power failure.
 )URPWKHPD[LPXPIUHTXHQF\
It is applicable to the power-generating load.