19
F1-03: Rated current of motor
If the motor is disconnected from the load completely, select “2” (complete tuning) in F1-11, and
press RUN in keypad, the inverter will calculate the parameters below automatically:
F1-06: Stator resistance F1-09: Mutual inductance
F1-07: Rotor resistance F1-10: Excitation current with no load
F1-08: Leakage inductance
Motor tuning is finished automatically.
If the motor cannot disconnect from its load, set F1-11 to 1(static tuning), and then press the RUN in
keypad. The inverter will measure the stator resistance, rotor resistance, leakage inductance,mutual
inductance and excitation current in sequence.