26
F6-00 Maximum frequency 50.0Hz ~ 3200.0Hz 0.1Hz 50.0Hz ×
F6-01 Frequency upper limit Frequency lower limit ~Maximum frequency 0.1Hz 0.0Hz
F6-02 Frequency lower limit 0.0 ~ frequency upper limit 0.1Hz 0.0Hz
F6-03 Carrier frequency 0.5kHz ~ 16.0kHz 0.1kHz
Depending
on the
inverter
model
F6-04 Jog frequency 0.0Hz ~ 50.0Hz 0.1Hz 2.0Hz
F6-05
Acceleration time 2
(Jog acceleration
time)
0.1s ~ 3000.0 s 0.0 20.0s
F6-06
Deceleration time 2
(Jog deceleration
time, also used as
the frequency
decrease time during
voltage
compensation)
0.1s ~ 3000.0s 0.0 20.0s
F6-07 Run reverse control
0: Run reverse enabled
1: Run reverse disabled
1 0
F6-08
FWD/REV dead zone
time
0.0s ~ 3000.0s 0.1s 0.0s
1
F6-09
Restart terminal
enable selection
0: Invalid
1: Valid
1 0
F6-10
Preset frequency
arrived checkout
value
0.0 ~100.0%(Maximum output frequency) 0.1% 0.0%
F6-12
Function of
STOP/RESET key
RESET function is valid in all status.
0: STOP function is invalid under terminal
control
1: Stop function is valid under terminal control
1 0