Function Code Table
MD380 User Manual
- 114 -
Function
Code
Parameter Name
Setting Range
Default Property
F9-54
Frequency selection for
continuing to run upon fault
0: Current running frequency
1: Frequency reference
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
0 ƿ
F9-55
Backup frequency upon
abnormality
0.0%–100.0%
The value 100.0% corresponds to
maximum frequency
100.0% ƿ
F9-56
Type of motor temperature
sensor
0: No temperature sensor
1: PT100
2: PT1000
1 ƿ
F9-57
Motor overheat protection
threshold
0–200°C
110
°C
ƿ
F9-58
Motor overheat pending
threshold
0–200°C
90
°C
ƿ
F9-59
Action selection at
instantaneous power failure
0: No action
1: Decelerate
2: Decelerate to stop
0 ƿ
F9-60
Judging voltage of action
disabled at instantaneous
power failure
80.0%–100.0%
90.0% ƿ
F9-61
Voltage recovery judging
time at instantaneous power
failure
0.00–100.00s
0.50s ƿ
F9-62
Judging voltage of action at
instantaneous power failure
60.0%–100.0% (standard bus
voltage)
80.0% ƿ
F9-63 Protection upon load lost
0: Disabled
1: Enabled
0 ƿ
F9-64 Load lost detection level
0.0%–100.0%
10.0% ƿ
F9-65 Load lost detection time
0.0–60.0s
1.0s ƿ
F9-67 2YHUVSHHGGHWHFWLRQOHYHO
0.0%–50.0% (maximum
frequency)
20.0% ƿ
F9-68 2YHUVSHHGGHWHFWLRQWLPH
0.0s: No detection
0.1–60.0s
1.0s ƿ
F9-69
Detection level of too large
speed feedback error
0.0%–50.0% (maximum
frequency)
20.0% ƿ
F9-70
Detection time of too large
speed feedback error
0.0s: No detection
0.1–60.0s
5.0s ƿ