7.5 Solutions to Current Leakage
The output of the AC drive is high-speed pulse voltage, producing high-frequency leakage
FXUUHQWGXULQJUXQQLQJRIWKH$&GULYH7RSUHYHQWHOHFWULFVKRFNDQGHYHQD¿UHFDXVHGE\
current leakage, it is necessary to install a residual current circuit-breaker for the AC drive.
Each AC drive produces more than 100 mA leakage current. Therefore, the sensitivity
current of the residual current circuit-breaker must be above 100 mA. High-frequency pulse
interference may cause the circuit-breaker to malfunction, and thus the residual current
FLUFXLWEUHDNHUPXVWKDYHWKHKLJKIUHTXHQF\¿OWHULQJIXQFWLRQ
If multiple AC drives are required, each AC drive must be installed with a circuit-breaker. The
IDFWRUVWKDWLQÀXHQFHWKHOHDNDJHFXUUHQWDUHDVIROORZV
 AC drive capacity
 Carrier frequency
 Type and length of motor cable
 (0,¿OWHU
:KHQWKHOHDNDJHFXUUHQWFDXVHVWKHFLUFXLWEUHDNHUWRDFW\RXVKRXOG
 Increase the sensitivity current of the circuit-breaker.
 Replace the circuit-breaker with a new one with high-frequency suppression function.
 Reduce the carrier frequency.
 Shorten the length of the output cable.
 Install a current leakage suppression device.