F0-07
Frequency source
superposition
selection
8QLWVGLJLW)UHTXHQF\VRXUFHVHOHFWLRQ
0
0: Main frequency source X
1: X and Y superposition
(superposition relationship determined by
ten's digit)
2: Switchover between X and Y
3: Switchover between X and "X and Y
superposition"
4: Switchover between Y and "X and Y
superposition"
Ten's digit (X and Y superposition
relationship)
0: X+Y
1: X-Y
2: MAX (X, Y)
3: MIN (X, Y)
It is used to select the frequency setting channel. The frequency reference is implemented
based on main frequency source X and auxiliary frequency source Y superposition.
Figure 6-1 Frequency setting based on main frequency source X and auxiliary frequency
source Y
Y
F0-05
F0-06
F0-07
unit's digit
Final
frequency
reference
X
+
|
Max
Min
0
1
2
3
0
1
2
3
4
F0-07
ten's digit
F4-00 to F4-09
18
DI1 to DI10
Frequency
switchover
X
Y
XY
Frequency
source selection
X and Y
superposition selection
Superposition
relationship
Target running
frequency
Amplitude
limit
If the frequency source involves X and Y superposition, you can set the frequency offset in F0-21,
ZKLFKLVDGGHGWRWKH;DQG<VXSHUSRVLWLRQUHVXOWWRÀH[LEO\VDWLVI\YDULRXVUHTXLUHPHQWV