Description of Function Codes
MD380 User Manual
- 198 -
Function Code Parameter Name Setting Range Default
F8-48
Cooling fan working
mode
:RUNLQJGXULQJUXQQLQJ
:RUNLQJFRQWLQXRXVO\
0
It is used to set the working mode of the cooling fan. If this parameter is set to 0, the fan
ZRUNVZKHQWKH$&GULYHLVLQUXQQLQJVWDWH:KHQWKH$&GULYHVWRSVWKHFRROLQJIDQ
works if the heatsink temperature is higher than 40°C, and stops working if the heatsink
temperature is lower than 40°C.
If this parameter is set to 1, the cooling fan keeps working after power-on.
Function Code Parameter Name Setting Range Default
F8-49 :DNHXSIUHTXHQF\
Hibernating frequency (F8-51) to
maximum frequency (F0-10)
0.00 Hz
F8-50 :DNHXSGHOD\WLPH 0.0–6500.0s 0.0s
F8-51 Hibernating frequency 0.00 Hz to wakeup frequency (F8-49) 0.00 Hz
F8-52 Hibernating delay time 0.0–6500.0s 0.0s
These parameters are used to implement the hibernating and wakeup functions in the water
supply application.
:KHQWKH$&GULYHLVLQUXQQLQJVWDWHWKH$&GULYHHQWHUVWKHKLEHUQDWLQJVWDWHDQGVWRSV
automatically after the hibernating delay time (F8-52) if the frequency reference is lower
than or equal to the hibernating frequency (F8-51).
:KHQWKH$&GULYHLVLQKLEHUQDWLQJVWDWHDQGWKHFXUUHQWUXQQLQJFRPPDQGLVHIIHFWLYHWKH
AC drives starts up after the wakeup delay time (F8-50) if the frequency reference is higher
than or equal to the wakeup frequency (F8-49).
Generally, set the wakeup frequency equal to or higher than the hibernating frequency. If
the wakeup frequency and hibernating frequency are set to 0, the hibernating and wakeup
functions are disabled.
:KHQWKHKLEHUQDWLQJIXQFWLRQLVHQDEOHGLIWKHIUHTXHQF\VRXUFHLV3,'ZKHWKHU3,'
operation is performed in the hibernating state is determined by FA-28. In this case, select
3,'RSHUDWLRQHQDEOHGLQWKHVWRSVWDWH)$ 
Function Code Parameter Name Setting Range Default
F8-53 Current running time reached 0.0–6500.0 min 0.0 min
,IWKHFXUUHQWUXQQLQJWLPHUHDFKHVWKHYDOXHVHWLQWKLVSDUDPHWHUWKHFRUUHVSRQGLQJ'2
EHFRPHV21LQGLFDWLQJWKDWWKHFXUUHQWUXQQLQJWLPHLVUHDFKHG
Function Code Parameter Name Setting Range Default
F8-54 2XWSXWSRZHUFRUUHFWLRQFRHI¿FLHQW 0.00%–200 .0% 100.0%
:KHQWKHRXWSXWSRZHU8LVQRWHTXDOWRWKHUHTXLUHGYDOXH\RXFDQSHUIRUPOLQHDU
correction on output power by using this parameter.