EasyManua.ls Logo

Inovance MD380 Series

Inovance MD380 Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Information MD380 User Manual
- 20 -
The housing types of the MD380 models with different voltage and power classes are listed
in the following table.
Table 2-1 Housing types for different voltage and power classes
Voltage & Power Class Housing Type
Single-phase 220 V
±N: Plastic housing
Three-phase 220 V
±N: Plastic housing
±N: Sheet metal housing
Three-phase 380 V
±N: Plastic housing
±N: Sheet metal housing
Three-phase 480 V
±N: Plastic housing
±N: Sheet metal housing
Three-phase 690 V
±N: Sheet metal housing
7HFKQLFDO6SHFL¿FDWLRQV
7DEOH7HFKQLFDOVSHFL¿FDWLRQVRIWKH0'
Item
6SHFL¿FDWLRQV
Standard
functions
Maximum
frequency
Vector control: 0–500 Hz
V/F control: 0–500 Hz
Carrier frequency
0.5–16 kHz
The carrier frequency is automatically adjusted based on
the load features.
Input frequency
resolution
Digital setting: 0.01 Hz
Analog setting: maximum frequency x 0.025%
Control mode
Sensorless vector control (SVC)
Closed-loop vector control (CLVC)
V/F control
Startup torque
G type: 0.5 Hz/150% (SVC); 0 Hz/180% (CLVC)
P type: 0.5 Hz/100%
Speed range
1:100 (SVC)
1:1000 (CLVC)
Speed stability
accuracy
f0.5% (SVC)
f0.02% (CLVC)
Torque control
accuracy
±5% (CLVC)