MD380 User Manual Operation, Display and Application Example
- 55 -
The switch signal mode is set in F4-11. The input terminal of the start/stop signal is set
in F4-00 to F4-09. For details, see the description of F4-11 and F4-00 to F4-09.
Example 1:
To use the DIP switch as the start/stop source, and allocate the forward rotation switch
signal to DI2 and the reverse rotation switch signal to DI3, perform the setting as shown
in the following gure.
Figure 4-6 Setting of using the DIP switch for start/stop
F4-00
F4-01
F4-02
F4-03
F4-04
.
.
1
2
.
.
F0-02 = 1
Running
command
F4-11 = 0
Control switch
Terminal
Function
code
Setting
value
Terminal
control
DI1
DI2
DI3
DI4
DI5
.
COM
RUN/
Fo rw a rd
Fo rw a rd R U N
Terminal control
Command source
selection
Two-line mode 1
RUN/
Reverse
Reverse R U N
SW2
SW1
In the preceding gure, when SW1 is ON, the AC drive instructs forward rotation; when
SW1 is OFF, the AC drive stops. When SW2 is ON, the AC drive instructs reverse
running; when SW2 is OFF, the AC drive stops. If SW1 and SW2 are ON or OFF
simultaneously, the AC drive stops.
Example 2:
To use the electromagnetic button as the start/stop source, and allocate the startup
signal to DI2, stop signal to DI3 and reverse rotation signal to DI4, perform the setting
as shown in the following gure.
Figure 4-7 Setting of using the electromagnetic button for start/stop
F4-00
F4-01
F4-02
F4-03
F4-04
.
.
1
2
3
.
F0-02 = 1
Running
command
F4-11 = 2
Control
button
Terminal
Function
code
Setting
value
Terminal
control
DI1
DI2
DI3
DI4
DI5
.
COM
RUN/
Fo rw a rd
STOP
Fo rw a rd R U N
Stop
Terminal control
Command
source selection
Three-line mode 1
RUN/
Reverse
Reverse R U N
SB2
SB1
SB3
In the preceding gure, SB1 must stay ON during normal start and running. The AC
drive stops immediately after SB1 becomes OFF. The signals from SB2 and SB3
become valid once they become ON. The running state of the AC drive is determined
by the nal actions on the three buttons.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD380T5.5GB and is the answer not in the manual?

Inovance MD380T5.5GB Specifications

General IconGeneral
Power5.5 kW
Input Voltage3-phase 380V AC
ModelMD380T5.5GB
CategoryDC Drives
Output Current12 A
Control ModeVector control
Frequency Range0 - 400 Hz
Cooling MethodForced Air Cooling
Storage Temperature-20°C to +60°C
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit
Humidity5% to 95% RH (non-condensing)
Altitude≤1000 m
Communication InterfaceRS485, Modbus
Operating Temperature-10°C to +40°C (derating above 40°C)