5.4.2 AC Input Reactor
An AC input reactor is an option used to eliminate harmonics of the input current.
Therefore, install an AC input reactor if the environment requires reduction of
harmonics.
If an AC input reactor is required for models with power over 200 kW, reserve
sufficient installation space in the cabinet for the reactor.
Models and dimensions (Inovance)
Recommended AC input reactor manufacturers and models are listed in the following
tables.
Figure 5‑15 AC input reactor model
Table 5–14 Selection of Inovance AC input reactors (three phase 380‑480 V)
Structure Model
Applicable Reactor
Inductance (mH) Loss (W)
T1
MD520‑4T0.4B(S)
MD‑ACL‑10‑5‑4T 5 50
MD520‑4T0.7B(S)
MD‑ACL‑10‑5‑4T 5 50
MD520‑4T1.1B(S)
MD‑ACL‑10‑5‑4T 5 50
MD520‑4T1.5B(S)
MD‑ACL‑10‑5‑4T 5 50
MD520‑4T2.2B(S)
MD‑ACL‑10‑5‑4T 5 50
MD520‑4T3.0B(S)
MD‑ACL‑10‑5‑4T 5 50
T2
MD520‑4T3.7B(S)
MD‑ACL‑15‑3‑4T 3 50
MD520‑4T5.5B(S)
MD‑ACL‑15‑3‑4T 3 50
T3
MD520‑4T7.5B(S)
MD‑ACL‑40‑1.45‑4T 1.45 100
MD520‑4T11B(S)
MD‑ACL‑40‑1.45‑4T 1.45 100
T4
MD520‑4T15B(S)
MD‑ACL‑50‑1.2‑4T 1.2 150
T5
MD520‑4T18.5(B)(S)
MD520‑4T18.5(B)(S)‑T
MD‑ACL‑50‑0.28‑4T‑2% 0.28
MD520‑4T22(B)(S)
MD520‑4T22(B)(S)‑T
MD‑ACL‑60‑0.24‑4T‑2% 0.24
T6
MD520‑4T30(B)(S)
MD‑ACL‑80‑0.17‑4T‑2% 0.17
MD520‑4T37(B)(S)
MD‑ACL‑90‑0.16‑4T‑2% 0.16
T7
MD520‑4T45(B)(S)
MD‑ACL‑120‑0.12‑4T‑2% 0.12
MD520‑4T55(B)(S)
MD‑ACL‑150‑0.095‑4T‑2% 0.095