1. Overview
Thank you for purchasing Inovance MD880 series active line module.
The MD880-40D series low-voltage and low-power active line module features high power density, compact
structure, and high reliability. It has a voltage class of 400 V, with rated power ranging from 64 kW to 271 kW. The
power module, 󶍾lter, controller, and detection unit of the line module are delivered separately to be integrated by
customers.
This user guide describes product information, installation instructions, and electrical connection. If you have any
question concerning the product function or performance, contact Inovance for technical support.
Document Acquisition
The user guide is not delivered together with the product. To purchase the user guide, contact the sales personnel.
2. Product Information
Model
.% % 
.
1SPEVDU5ZQF
"DUJWFMJOFNPEVMF
JOUFHSBUFELJU
.%
1SPEVDU4FSJFT
.%TFSJFT

3BUFE$VSSFOU
"
7PMUBHF$MBTT
QIBTF7"$
%
"DUJWFMJOFNPEVMF
$PEF $PEF $PEF $PEF
Figure 1 Model description
Speci󶍾cations and model selection
Table 1 Speci󶍾cations and selection of MD880-40D series active line module
Active line module
model
Power module model
Application without overload
Application
with light
overload
Application
with heavy
overload
Thermal
design
power
Air
volume
I
N
I
N
I
max
S
N
P
N
I
Ld
P
Ld
I
Hd
P
Hd
P
loss
m
3
/h
A
ac
A
dc
A
dc
kVA kW A
dc
kW A
dc
kW kW
MD880-40D-0094-4 MD880-40M-0094-4 94 107 140 65 64 103 62 81 48 1.60 178
MD880-40D-0149-4 MD880-40M-0149-4 149 170 221 103 102 164 98 128 77 2.55 297
MD880-40D-0183-4 MD880-40M-0183-4 183 209 272 127 126 201 120 157 94 3.15 331
MD880-40D-0299-4 MD880-40M-0299-4 299 342 444 207 205 328 197 256 154 5.12 420
MD880-40D-0395-4 MD880-40M-0395-4 395 452 587 274 271 433 260 339 203 6.77 700
I
N
:
Rated input (AC)/output (DC) current
I
max
: Maintaining the max. output current for at least 10s (every 300s) upon start
S
N
: Apparent power
P
N
: Rated output power
I
Ld
: Continuous output current in applications with light overload
P
Ld
: Output power in applications with light overload
I
Hd
: Continuous output current in applications with heavy overload
P
Hd
: Output power in applications with heavy overload
1
MD880-40D Series
Active Line Module
*19012241A00*
19012241A00
P
loss
: Total loss of active line module
Table 2 Fuse selection
Model Type Model (SINOFUSE) Speci󶍾cations Quantity
0094-4
AC fuse RS306-1-W1Z-125A690V 125 A, 690 V 3
DC fuse RS306-1-W1Z-160A690V 160 A, 690 V 2
0149-4
AC fuse RS306-1-W1Z-200A690V 200 A, 690 V 3
DC fuse RS306-1-W1Z-250A690V 250 A, 690 V 2
0183-4
AC fuse RS306-1-W1Z-250A690V 250 A, 690 V 3
DC fuse RS306-1-W1Z-315A690V 315 A, 690 V 2
0299-4
AC fuse RS306-1-W1Z-400A690V 400 A, 690 V 3
DC fuse RS306-1-W1Z-450A690V 450 A, 690 V 2
0395-4
AC fuse RS306-1-W1Z-550A690V 550 A, 690 V 3
DC fuse RS306-1-W1Z-630A690V 630 A, 690 V 2
Technical Data
Item Name Speci󶍾cations
Basic
performance
AC input voltage 400 V system: 380 VAC to 415 VAC, ±10% (-15%, < 1 min)
Input frequency 47 Hz to 63 Hz
Degree of voltage
unbalance
±3% of rated voltage at most
Output voltage 400 V system: 540 VDC to 720 VDC
Overload capacity
Light overload: Operating continuously for 1 min every 5 min upon 110% ILd
Heavy overload: Operating continuously for 1 min every 5 min upon 150% IHd
Basic
performance
Operating e󶎀ciency More than 97%
Power factor > 0.99 (at rated power with full load)
Total harmonics THD
THDI < 5% (rated power)
THDU < 5% (Rsc > 20)
Operating
environment
Ambient temperature -10℃ to +40℃ , derating required for temperatures between 40℃ to 50℃
Relative humidity 5% to 95%, without condensation
Altitude
≤ 1000 m: derating not required
> 1000 m: derating required
Max.: 4000 m
Storage
Storage temperature -40° C to +70° C
Storage humidity 5% to 95%, without condensation
Mechanical
data
Vibration resistance
Compliant with vibration class 3M4 in GB/T4798.3
Steady-state sinusoidal vibration: 2–9 Hz, 3 mm
9–200 Hz, 10 m/s
2
Impact: 100 m/s
2
, 11 ms
IP rating
Module: IP00
Cabinet: IP21
Safety performance Compliant with EN 61800-5-1
Cooling method
Forced air cooling (AF), compliant with EN 60146 for the module
Natural cooling for the reactor
Protective
functions
Protective functions
Providing protection against short circuit, overcurrent, overload, overvoltage,
undervoltage, phase loss, three-phase unbalance, and overtemperature
3. Electrical Wiring
The following 󶍾gure shows the electrical wiring of MD880-40D series active line module integrated
kit.
FROM-
HSVM1
Buffer
contactor
KM2
control
Fault
output
Main
contactor
KM1
control
Reactor feedback signal
Reset signal
Stop control
Main contactor feedback signal
Start control
E-stop
AC input
40D buffer units
Buffer contactor
Buffer contactor
control
Main contactor
DC bus (+)
DC bus (-)
Figure 3 Electrical wiring
Table 3 List of deliverables
No. Name Description
1
HOFM-30 optical 󶍾ber
extension module
Connected to HCU through the SLOT to provide multiple optical 󶍾ber interfaces
for HCU.
2 HCU controller module
Connected to line module U1 through the electrical interface to be used as the
controller for MD880-40D.
3
SOP-20 smart
operating panel
Connected to the HCU through the network cable to perform parameter setting,
software programming, start/stop control, and communication relay on the
active line module (including the operating panel base).
4 Main contactor Used to control switch-on/o󶍽 of the three-phase incoming cables.
5
Reactor on the power
grid side
Small reactor of LCL 󶍾lter
6
Reactor on the line
module side
Large reactor of LCL 󶍾lter
7 Active line module Power module of the active line module
8 Bu󶍽er components Providing DC bus bu󶍽er circuit for the active line module
9 Capacitor module Three-phase capacitor module
10 HSVM-10
Synchronous voltage module to collect incoming voltage for the active line
module
NOTE
T
able 2 lists recommended fuse models.
Table 3 lists the deliverables. Components not listed are to be con󶍾gured by customers.
The terminal block is not available for the capacitor module of the bolt 󶍾xing terminal. Perform
wiring based on the label of the copper busbar.
4. Technical Data for Installation
Dimensions of the line module
1) H3







%$XJSJOHUFSNJOBM
"$XJSJOHUFSNJOBM
Figure 4 H3 dimensions (unit:mm)
Structure Line module model Wiring hole diameter
H3 MD880-40M-0094-4 M6
2) H4




%$XJSJOHUFSNJOBM
"$XJSJOHUFSNJOBM



Figure 5 H4 dimensions (unit:mm)
Structure Line module model Wiring hole diameter
H4
MD880-40M-0149-4
M10