29
Range - letters and numerals, max.16 characters
Default
value
- Name of resource (I1…I8)
Comments - Using friendly names facilitates recognition of destination
and appropriate settings.
7.2.5.2.2.2. Operation mode
Function - defines operating mode for inputs I1…I8
Data type - selection list
List - Binary input
the input acts as typical binary input accepting positive and
negative logic.
Counter input
the input acts as counter input. Each pulse appearing on
input increments value of corresponding 32 bit register
Default
value
- Binary input
Comments - selecting appropriate operating mode is the basis for taking
full advantage of module capabilities. It has an influence on
available configuration parameters optimizing module
performance.
7.2.5.2.2.2.1. Binary input
7.2.5.2.2.2.1.1. Filtering constant
Function - Defines (in seconds) value of min. duration of
altered state on input in order to consider state to
be stable.
Data type - number
Range - 0,00…163,83 [s]
Default value -0,1 [s]
Comments - Setting value appropriate to contact characteristics
eliminates disturbance caused by contact bounce
thus preventing multiple registration of what is in
reality one pulse.
7.2.5.2.2.2.2. Counter input
7.2.5.2.2.2.2.1. Counting direction
Function - defines counting direction
Data type - selection list
Range - Up
A pulse on input increases value of counter register
Down
A pulse on input decreases value of counter register
Default value - Up
Comments - The counting process is valid only within range of
Counting range parameter.