7.2.5.2.4.3. Engineering units
Function - Defines a name for engineering units for measured values.
Data type - text
Range - letters and numerals, max 16 characters
Default
value
- x
Comments - inserted text does not have any influence on the value of
measured analogue signal
7.2.5.2.4.4. Low reference - internal units
Function - used along with other reference parameters for rescaling
input signal range to engineering units range
Data type - number
Range - 0…1000
Default
value
- 40
Comments - low reference point for internal units
7.2.5.2.4.5. Low reference - engineering units
Function - used along with other reference parameters for rescaling
input signal range to engineering units range
Data type - number
Range - 0…10000
Default
value
- 40
Comments - low reference point for engineering units
7.2.5.2.4.6. High reference - internal units
Function - used along with other reference parameters for rescaling
input signal range to engineering units range
Data type - number
Range - 1…1000
Default
value
- 200
Comments - high reference point for internal units
7.2.5.2.4.7. High reference - engineering units
Function - used along with other reference parameters for rescaling
input signal range to engineering units range
Data type - number
Range - 1…10000
Default
value
- 200
Comments - high reference point for engineering units