7.2.5.2.2.2.2.2. Counting range
Function - defines max. value assumed by the counter
Data type - number
Range - 0…2 147 483 647 (31 bits + counting direction bit)
Default value -0
Comments - when counting up the counter is zeroed by next
appearing pulse upon reaching declared value.
When counting down, next pulse writes declared
value into the counter upon reaching 0. 0 (zero)
value switches counting off.
7.2.5.2.2.2.2.3. Filtering constant
Function - Defines (in seconds) value of min. duration of
altered state on input in order to consider state to
be stable.
Data type - number
Range - 0,00…163,83 [s]
Default value -0,1 [s]
Comments - Setting value appropriate to contact characteristics
eliminates disturbance caused by contact bounce
thus preventing multiple registration of what is in
reality one pulse.
7.2.5.2.3. Binary outputs Q1, Q2
MT-301 and MT-303 modules are equipped with respectively two and one Binary
outputs. Besides standard functionality outputs of MT-301 can be configured for driving
external analog inputs multiplexer increasing number of available analog inputs.
7.2.5.2.3.1. Name
Function - Enables entering friendly name of input e.g. connected to
the function performed. The name is displayed on terminals
list.
Data type - text
Range - letters and numerals, max.16 characters
Default
value
- Name of resource (I1…I8)
Comments - Using friendly names facilitates recognition of destination
and appropriate settings.
7.2.5.2.3.2. Operation mode
Function - defines operating mode for outputs Q1, Q2
Data type - selection list
List - Binary output
the output acts as typical positive logic binary output.
Default
value
- Binary output
Comments - n/a