List of Function Parameters 
 
92
Function 
Code 
Name  Description 
Factory 
Setting
Modify 
Serial 
No. 
P5.05 
FWD/REV control 
mode 
0: 2-wire control mode 1 
1: 2-wire control mode 2 
2: 3-wire control mode 1 
3: 3-wire control mode 2 
0 
 
58 
P5.06 
UP/DOWN setting 
change rate 
0.01~50.00Hz/s 
0.50 
Hz/s 
O  59 
P5.07 
AI1 lower limit  0.00V~10.00V 
0.00V O  60 
P5.08 
AI1 lower limit 
corresponding 
setting  
-100.0%~100.0% 
0.0% O  61 
P5.09 
AI1 upper limit  0.00V~10.00V 
10.00V O  62 
P5.10 
AI1 upper limit 
corresponding 
setting 
-100.0%~100.0% 
100.0% O  63 
P5.11 
AI1 filter time 
constant 
0.00s~10.00s 
0.10s O  64 
P5.12 
AI2 lower limit  0.00V~10.00V 
0.00V O  65 
P5.13 
AI2 lower limit 
corresponding 
setting 
-100.0%~100.0% 
0.0% O  66 
P5.14 
AI2 upper limit  0.00V~10.00V 
10.00V O  67 
P5.15 
AI2 upper limit 
corresponding 
setting 
-100.0%~100.0% 
100.0% O  68 
P5.16 
AI2 filter time 
constant 
0.00s~10.00s 
0.10s O  69 
P6 Group: Output Terminals 
P6.00  Y output selection  1  O  70 
P6.01 
Relay output 
selection 
0: No output 
1: Run forward 
2: Run reverse 
3: Fault output 
4: FDT reached 
5: Frequency reached 
6: Zero speed running 
7: Upper frequency limit reached 
8: Lower frequency limit reached 
9~10: reserved 
3  O  71