CHE Series Sensorless Vector
Control Inverter
Operation Manual
z Thank you very much for your buying CHE series sensorless vector control
inverter.
z
Before use, please read this manual thoroughly to ensure proper usage. Keep this
manual at an easily accessible place so that can refer anytime as necessary.

Table of Contents

Questions and Answers

  • M
    Michael LevineAug 20, 2025
    What to do if there is over-current during acceleration in INVT DC Drives?
    • D
      Dennis KelleyAug 21, 2025
      If the INVT DC Drive displays an over-current error during acceleration, it could be due to several reasons. There might be a short-circuit or ground fault at the inverter output, the load could be too heavy, the acceleration/deceleration time might be too short, the V/F curve might be unsuitable, or there could be a sudden change in load. To resolve this: * Inspect the motor for damage, worn insulation, or cable damage. * Increase the acceleration/deceleration time or select an inverter with a larger capacity. * Check and adjust the V/F curve, and also check the load.
  • J
    Jeffrey RichardsAug 22, 2025
    Why is my INVT DC Drives showing inverter overload?
    • M
      Michael CookAug 22, 2025
      If your INVT DC Drive displays an inverter overload, it could be due to a heavy load, short acceleration/deceleration time, an unsuitable V/F curve, or the inverter's capacity being too small. Here's how to address it: * Increase the acceleration/deceleration time or choose an inverter with a larger capacity. * Check and adjust the V/F curve. * Consider selecting an inverter with a higher capacity.
  • L
    Leslie BennettAug 25, 2025
    How to fix IGBT Ph-U fault in INVT CHE100-0R4G-S2 DC Drives?
    • D
      David MooreAug 25, 2025
      If the INVT DC Drive shows an IGBT Ph-U fault, it could be due to several reasons: the acceleration/deceleration time being too short, a fault in the IGBT module itself, malfunction caused by interference, or improper grounding. To address this: * Increase the acceleration/deceleration time. * Inspect external equipment and eliminate any interference.
  • R
    rebeccaherreraAug 27, 2025
    What causes over-voltage during acceleration in INVT DC Drives?
    • C
      Charles MasonAug 27, 2025
      If the INVT DC Drive shows an over-voltage error during acceleration, it could be due to a short deceleration time causing excessive regenerative energy from the motor, or the input voltage being too high. To fix this, you can: * Increase the deceleration time or connect a braking resistor. * Decrease the input voltage to stay within the specified range.
  • R
    robinsonkimberlyAug 28, 2025
    Why is my INVT DC Drives showing motor overload?
    • D
      Derrick BentleyAug 28, 2025
      If the INVT DC Drive indicates a motor overload, it may be because the motor is driving a heavy load at low speed for an extended period, the V/F curve is not properly set, the motor’s overload protection threshold (PB.01) is incorrect, or there is a sudden load change. To resolve this: * Select a variable frequency motor. * Check and adjust the V/F curve. * Check and adjust PB.01. * Check the load.
  • S
    Sarah BakerAug 29, 2025
    What causes DC bus Under-voltage in INVT CHE100-0R4G-S2?
    • D
      Dalton HallAug 29, 2025
      If the INVT DC Drive displays a DC bus under-voltage error, it could be due to an open phase in the power supply, a momentary power loss, loose wiring terminals for the input power supply, or large voltage fluctuations in the power supply. Inspect the input power supply or wiring.
  • N
    Nicholas RogersAug 31, 2025
    What to do if INVT CHE100-0R4G-S2 DC Drives shows input phase failure?
    • Q
      qreidAug 31, 2025
      If the INVT DC Drive shows an input phase failure, it could be due to an open phase in the power supply, a momentary power loss, loose wiring terminals for the input power supply, large voltage fluctuations in the power supply, or poor voltage balance between phases. Check the wiring, installation, and power supply.
  • K
    Katie GraySep 2, 2025
    How to resolve rectify overheat in INVT CHE100-0R4G-S2 DC Drives?
    • A
      Ashley ValdezSep 2, 2025
      If the INVT DC Drive displays a rectify overheat error, it could be due to high ambient temperature, proximity to a heat source, cooling fan issues (stopped or damaged), obstructed ventilation, or a high carrier frequency. To solve this: 1. Install a cooling unit. 2. Remove any nearby heat sources. 3. Replace the cooling fan. 4. Clear any obstructions in the ventilation channel. 5. Decrease the carrier frequency.
  • K
    Kelsey SnyderSep 4, 2025
    What causes output phase failure in INVT DC Drives?
    • G
      gilbertmichaelSep 4, 2025
      If the INVT DC Drive indicates an output phase failure, it could be due to a broken wire in the output cable, a broken wire in the motor winding, or loose output terminals. Check the wiring and installation.
  • R
    Rhonda Lee DVMSep 6, 2025
    How to troubleshoot communication fault in INVT CHE100-0R4G-S2 DC Drives?
    • S
      Stephanie WallSep 6, 2025
      If the INVT DC Drive displays a communication fault, it may be due to an incorrect baud rate setting, receiving incorrect data, or a prolonged interruption in communication. To solve this, set the proper baud rate and check the communication devices and signals.

Summary

Safety Precautions

Introduction

Technology Features

Details input/output, I/O features, and main control functions of the inverter.

Description of Name Plate

Explains the information presented on the inverter's nameplate.

Selection Guide

Provides a table to help select the correct inverter model based on specifications.

Installation

Environmental Requirements

Specifies conditions like temperature, humidity, altitude, and vibration for installation.

Wiring

Terminal Configuration

Details main and control circuit terminal layouts for different inverter sizes.

Main Circuit Wiring

Explains wiring for input, output, and common DC bus connections.

Control Circuit Wiring

Details wiring precautions and terminal functions for control circuits.

Operation

Detailed Function Description

Trouble Shooting

Fault and Troubleshooting Guide

Lists common fault codes, their reasons, and recommended solutions.

Common Faults and Solutions

Provides solutions for common operational issues like no display or motor not moving.

Maintenance

INVT CHE100-0R4G-S2 Specifications

General IconGeneral
ModelCHE100-0R4G-S2
Power0.4 kW
Control ModeV/F control
Communication InterfaceRS485
Humidity5% to 95% (Non-condensing)
Enclosure RatingIP20
Frequency Range0-400 Hz
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Overload
Ambient Temperature-10°C to 40°C
Storage Temperature-20°C to 60°C
AltitudeUp to 1000m
Voltage ClassSingle-phase 220V