EasyManuals Logo

INVT DBU100H Series User Manual

INVT DBU100H Series
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
Operational manual for dynamic braking unit
-18-
Power
Model
100% of the
adaptation
braking
resistor of
the braking
torque(Ω)
Dissipated
power of the
braking
resistor(kW)
(10% of the
braking)
Dissipated
power of the
braking
resistor(kW)
(50% of the
braking)
Dissipated
power of the
braking
resistor(kW)
(80% of the
braking)
Mini
allowable
braking
resistor(Ω)
37kW
DBU100H-060-4
13.2
6
28
44
11.7
45kW
DBU100H-110-4
10.9
7
34
54
6.4
55kW
8.9
8
41
66
75kW
6.5
11
56
90
90kW
DBU100H-160-4
5.4
14
68
108
4.4
110kW
4.5
17
83
132
132kW
DBU100H-220-4
3.7
20
99
158
3.2
160kW
DBU100H-320-4
3.1
24
120
192
2.2
200kW
2.5
30
150
240
220kW
DBU100H-400-4
2.2
33
165
264
1.8
250kW
2.0
38
188
300
280kW
Two
DBU100H-320-4
3.6*2
21*2
105*2
168*2
2.2*2
315kW
3.2*2
24*2
118*2
189*2
350kW
2.8*2
27*2
132*2
210*2
400kW
2.4*2
30*2
150*2
240*2
500kW
Two
DBU100H-400-4
2*2
38*2
186*2
300*2
1.8*2
8.6 Usage standard and selection reference of the input voltage degree
for adaptation DBU (660V)
Below is the selection reference when the DC operating point of the braking unit is 1100V: