Goodrive20-EU series VFD    Peripheral options and parts 
152 
Note:  A  separate  PE  conductor  is  required  if  the  conductivity  of  the  cable  shield  is  not 
sufficient for the purpose. 
C.3.2 Control cables 
All analog control cables and the cable used for the frequency input must be shielded.   
The relay cable needs the cable type with braided metallic screen. 
Note: Run analog and digital signals in separate cables. 
Check the insulation of the input power cable according to local regulations before connecting 
to the drive. 
Recommended 
cable size (mm
2
) 
Connecting cable size 
(mm
2
)