Goodrive20-EU series VFD    Function parameters 
32 
5 Function parameters 
The function parameters of Goodrive20-EU series VFDs  have been divided into 30 groups 
(P00 – P29) according to the function, of which P18 – P28 are reserved. Each function group 
contains certain function codes applying 3-level menus. For  example, "P08.08" means  the 
eighth function code in the P8 group function, P29 group is factory reserved, and users are 
forbidden to access these parameters.   
For the convenience of function codes setting, the function group number corresponds to the 
first level  menu,  the  function code corresponds to the second  level menu and the  function 
code corresponds to the third level menu.   
1. Below is the instruction of the function lists:   
The first column "Function code": codes of function parameter group and parameters; 
The second column "Name": full name of function parameters; 
The third  column  "Detailed  illustration of parameters": Detailed  illustration of  the  function 
parameters; 
The fourth column "Default value": the original factory set value of the function parameter; 
The fifth column "Modify": the modifying character of function codes (the parameters can be 
modified or not and the modifying conditions), below is the instruction: 
"○": means the set value of the parameter can be modified in stop and running state; 
"◎": means the set value of the parameter cannot be modified in the running state; 
"●": means the value of the parameter is the real detection value which cannot be modified. 
Detailed instruction of parameters 
P00 Group    Basic function group 
0: SVC 0 
No need to install encoders. Suitable in 
applications which need low frequency, big 
torque for high accuracy of rotating speed and 
torque control. Relative to mode 1, it is more 
suitable for the applications which need small 
power. 
1: SVC 1   
1 is suitable in high performance cases with the 
advantage of high accuracy of rotating speed 
and torque. It does not need to install pulse 
encoder.