Goodrive20-EU series VFD    Communication protocol 
133 
VFD
address
Read
command
  Parameters
data
 
CRC check 2-byte
data
 
Because the parameter data is 0032H (50) and 50 divided by 10 is 5, then the hibernation 
restore delay time is 5s. 
7.4.4 Fault message response   
There may be fault in the communication control. For example, some parameter can only be 
read. If a writing message is sent, the VFD will return a fault response message.   
The fault message is from the VFD to the master, its code and meaning is as follows:   
The  command  from  master  cannot  be  executed.  The 
reason maybe: 
1. This command is only for new version and this version 
cannot realize. 
2. Slave is in fault state and cannot execute it. 
Some  of  the  operation  addresses  are  invalid  or  not 
allowed  to  access.  Especially  the  combination  of  the 
register and the transmitting bytes are invalid.   
When  there  are  invalid  data  in  the  message  framed 
received by slave. 
Note: This error code does not indicate the data value to 
write exceed the range, but indicate the message frame is 
an illegal frame. 
The parameter setting in parameter writing is invalid. For 
example,  the  function  input  terminal  cannot  be  set 
repeatedly.   
The password written to the password check address is 
not same as the password set by P7.00. 
In  the  frame  message  sent  by  the  upper  monitor,  the 
length of the digital frame is incorrect or the counting of 
CRC check bit in RTU is different from the lower monitor.   
It only happen in write command, the reason maybe: 
1. The written data exceeds the parameter range. 
2. The parameter should not be modified now. 
3. The terminal has already been used. 
The parameter cannot 
be modified during 
running 
The modified parameter in the writing of the upper monitor 
cannot be modified during running.