Goodrive20-EU series VFD    Function parameters 
80 
Detailed instruction of parameters 
two-phase modulation   
1: PWM mode 2, three-phase modulation 
LED tens: low-speed carrier frequency limit 
mode 
0: Low-speed carrier frequency limit mode 1, the 
carrier frequency will limit to 1k or 2k if it exceeds 
2k at low speed   
1: Low-speed carrier frequency limit mode 2, the 
carrier frequency will limit to 4k if it exceeds 4k at 
low speed   
2: No limit 
LED ones 
0: Disabled 
1: Enabled 
LED tens 
0: Light overmodulation; restricted in zone 1 
1: Heavy overmodulation; restricted in zone 2 
For VFDs of 1PH 220V/3PH 380V (≤2.2kW) and 
3PH 220V (≤0.75kW), the default value is 00;   
for those of 3PH 380V (≥4kW) and 3PH 220V 
(≥1.5kW), the default value is 01. 
Keypad digital 
control setting 
0x0000 – 0x1223 
LED ones: frequency enable selection   
0: Both  ∧/∨  keys and analog potentiometer 
adjustments are valid   
1: Only  ∧/∨  keys adjustment is valid 
2: Only analog potentiometer adjustments is 
valid 
3: Neither  ∧/∨  keys nor digital potentiometer 
adjustments are valid 
LED tens: frequency control selection 
0: Valid only when P00.06=0 or P00.07=0 
1: Valid for all frequency setting modes 
2: Invalid for multi-step speed when multi-step 
speed has the priority   
LED hundreds: action selection during stopping 
0: Setting is valid   
1: Valid during running, cleared after stopping