Goodrive20 inverters Function Parameters
34
Function
code
Name Detailed instruction of parameters
Default
value
Modify
Note: This function is only available for the inverters≥4kW
Starting
frequency of
direct start-up
Starting frequency of direct start-up means the original
frequency during the inverter starting. See P01.02 for
detailed information.
Setting range: 0.00~50.00Hz
0.50Hz
Retention time
of the starting
frequency
Set a proper starting frequency to increase the torque of the
inverter during starting. During the retention time of the
starting frequency, the output frequency of the inverter is the
starting frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set frequency
is lower than the starting frequency, the inverter will stop
running and keep in the stand-by state. The starting
frequency is not limited in the lower limit frequency.
Setting range: 0.0~50.0s
0.0s ◎
The braking
current before
starting
The inverter will carry out DC braking at the braking current
set before starting and it will speed up after the DC braking
time. If the DC braking time is set to 0, the DC braking is
invalid.
The stronger the braking current, the bigger the braking
power. The DC braking current before starting means the
percentage of the rated current of the inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.00~50.00s
0.0% ◎
The braking
time before
starting
0.00s ◎
ACC/DEC
selection
The changing mode of the frequency during start-up and
running.
0:Linear type
The output frequency increases or decreases linearly.
0 ◎