Goodrive20-EU series VFD Peripheral options and parts
152
Note: A separate PE conductor is required if the conductivity of the cable shield is not
sufficient for the purpose.
C.3.2 Control cables
All analog control cables and the cable used for the frequency input must be shielded.
The relay cable needs the cable type with braided metallic screen.
Note: Run analog and digital signals in separate cables.
Check the insulation of the input power cable according to local regulations before connecting
to the drive.
Model
Recommended
cable size (mm
2
)
Connecting cable size
(mm
2
)
Terminal
screw
Tightening
torque (Nm)
RST
PE
RST
P1, (+)
PE
UVW
UVW
GD20-0R4G-S2-EU
1.5
1.5
1 4
1 4
1 4
M3
0.8
GD20-0R7G-S2-EU
1.5
1.5
1 4
1 4
1 4
M3
0.8
GD20-1R5G-S2-EU
2.5
2.5
1 4
1 4
1 4
M3
0.8
GD20-2R2G-S2-EU
2.5
2.5
1 4
1 4
1 4
M3
0.8
GD20-0R4G-2-EU
1.5
1.5
1-1.5
1-1.5
1-1.5
M3
0.8
GD20-0R7G-2-EU
1.5
1.5
1-1.5
1-1.5
1-1.5
M3
0.8
GD20-1R5G-2-EU
2.5
2.5
1.5 6
2.5 6
2.5 6
M4
1.13
GD20-2R2G-2-EU
2.5
2.5
1.5 6
2.5 6
2.5 6
M4
1.13
GD20-004G-2-EU
2.5
2.5
1.5 6
2.5 6
2.5 6
M4
1.13
GD20-5R5G-2-EU
4
4
4 10
4 10
4 10
M5
2.3
GD20-7R5G-2-EU
6
6
4 10
4 10
4 10
M5
2.3
GD20-0R7G-4-EU
1.5
1.5
1-1.5
1-1.5
1-1.5
M3
0.8
GD20-1R5G-4-EU
1.5
1.5
1-1.5
1-1.5
1-1.5
M3
0.8
GD20-2R2G-4-EU
1.5
1.5
1-1.5
1-1.5
1-1.5
M3
0.8
GD20-004G-4-EU
2.5
2.5
2.5 6
2.5 6
2.5 6
M4
1.13
GD20-5R5G-4-EU
2.5
2.5
2.5 6
2.5 6
2.5 6
M4
1.13
GD20-7R5G-4-EU
4
4
4 10
4 10
4 10
M5
2.3
GD20-011G-4-EU
6
6
4 10
4 10
4 10
M5
2.3
GD20-015G-4-EU
6
6
4 10
4 10
4 10
M5
2.3
GD20-018G-4-EU
10
10
10 16
10 16
10 16
M5
2.3
GD20-022G-4-EU
16
16
10 16
10 16
10 16
M5
2.3
GD20-030G-4-EU
25
16
25 50
25 50
16 25
M6
2.5
GD20-037G-4-EU
25
16
25 50
25 50
16 25
M6
2.5
GD20-045G-4-EU
35
16
35 70
35 70
16 35
M8
10