– 50.00kHz. 
100.0% of the high speed pulse input setting 
corresponds to the maximum frequency in 
forward direction (function code P00.03) and 
-100.0% corresponds to the maximum frequency 
in reverse direction (function code P00.03). 
Note: The pulse setting can only be input by 
multi-function terminals HDI. Set P05.00 (HDI 
input selection) to high speed pulse input. 
5: Set via simple PLC program 
The VFD runs at simple PLC program mode 
when P00.06=5 or P00.07=5. Set P10 (simple 
PLC and multi-step speed control) to select the 
running frequency running direction, 
acceleration/deceleration time and the keeping 
time of corresponding stage. See the function 
description of P10 for detailed information.   
6: Set via multi-step speed running 
The VFD runs at multi-step speed mode when 
P00.06=6 or P00.07=6. Set P05 to select the 
current running step, and set P10 to select the 
current running frequency.   
The multi-step speed has the priority when 
P00.06 or P00.07 does not equal to 6, but the 
setting stage can only be the 1 – 15 stage. The 
setting stage is 1 – 15 if P00.06 or P00.07 equals 
to 6. 
7: Set via PID control 
The running mode of the VFD is process PID 
control when P00.06=7 or P00.07=7. It is 
necessary to set P09. The running frequency of 
the VFD is the value after PID effect. See P09 for 
the detailed information of the preset source, 
preset value and feedback source of PID.   
8: Set via MODBUS communication 
The frequency is set by MODBUS 
communication. See P14 for detailed 
information. 
9 – 11: Reserved