Goodrive20 inverters Function Parameters
36
Function
code
Name Detailed instruction of parameters
Default
value
Modify
DC braking
time
rated current of inverter. The bigger the DC braking current
is, the greater the braking torque is.
DC braking time: the retention time of DC braking. If the
time is 0, the DC braking is invalid. The inverter will stop at
the set deceleration time.
Setting range of P01.09: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P01.10: 0.00~50.00s
Setting range of P01.11: 0.0~100.0%
Setting range of P01.12: 0.00~50.00s
0.00s
○
Dead time of
FWD/REV
rotation
During the procedure of switching FWD/REV rotation, set
the threshold by P01.14, which is as the table below:
Setting range: 0.0~3600.0s
0.0s ○
Switching
between
FWD/REV
rotation
Set the threshold point of the inverter:
0:Switch after zero frequency
1:Switch after the starting frequency
2: Switch after the speed reach P01.15 and delay for
P01.24
0 ◎
Stopping
speed
0.00~100.00Hz 0.50Hz
Detection of
stopping speed
0: Detect at the setting speed
1: Detect at the feedback speed(only valid for vector control)