Goodrive20 inverters Function Parameters
66
Function
code
Name Detailed instruction of parameters
Default
value
Modify
The setting range of P08.16: 0.0~50.0%
(relative to the traverse range)
The setting range of P08.17: 0.1~3600.0s
The setting range of P08.18: 0.1~3600.0s
P08.25
The counter works by the input pulse signals of the HDI
terminals.
When the counter achieves a fixed number, the
multi-function output terminals will output the signal of “fixed
counting number arrival” and the counter go on working;
when the counter achieves a setting number, the
multi-function output terminals will output the signal of
“setting counting number arrival”, the counter will clear all
numbers and stop to recount before the next pulse.
The setting counting value P08.26 should be no more than
the setting counting value P08.25.
The function is illustrated as below:
Setting range of P08.25:P08.26~65535
Setting range of P08.26:0~P08.25
0
○
time
Pre-set running time of the inverter. When the accumulative
running time achieves the set time, the multi-function digital
output terminals will output the signal of “running time
arrival”.
Setting range:0~65535min
0m ○
Time of fault
reset
The time of the fault reset: set the fault reset time by
selecting this function. If the reset time exceeds this set
value, the inverter will stop for the fault and wait to be
repaired.
The interval time of the fault reset: The interval between the
time when the fault occurs and the time when the reset
action occurs.
Setting range of P08.28:0~10
Setting range of P08.29:0.1~100.0s
0 ○
automatic fault
reset
1.0s ○
Frequency
decreasing
ratio in drop
control
The output frequency of the inverter changes as the load.
And it is mainly used to balance the power when several
inverters drive one load.
Setting range: