Setting range: 1 – 247   
When the master is writing the frame, the 
communication address of the slave is set to 0; 
the broadcast address is the communication 
address. All slaves on the MODBUS fieldbus can 
receive the frame, but the salve doesn't answer. 
The communication address of the drive is 
unique in the communication net. This is the 
fundamental for the point to point communication 
between the upper monitor and the drive.   
Note: The address of the slave cannot set to 0.   
Set the digital transmission speed between the 
upper monitor and the VFD.   
0: 1200BPS 
1: 2400BPS 
2: 4800BPS 
3: 9600BPS 
4: 19200BPS 
5: 38400BPS 
6: 57600BPS 
Note: The baud rate between the upper monitor 
and the VFD must be the same. Otherwise, the 
communication is not applied. The bigger the 
baud rate, the quicker the communication speed.   
The data format between the upper monitor and 
the VFD must be the same. Otherwise, the 
communication is not applied. 
0: No parity check (N, 8, 1) for RTU 
1: Even parity check (E, 8, 1) for RTU 
2: Odd parity check (O, 8, 1) for RTU 
3: No check (N, 8, 2) for RTU 
4: Even parity check (E, 8, 2) for RTU 
5: Odd parity check (O, 8, 2) for RTU 
6: No check (N, 7, 1) for ASCII 
7: Even check (E, 7, 1) for ASCII 
8: Odd check (O, 7, 1) for ASCII 
9: No check (N, 7, 2) for ASCII 
10: Even check (E, 7, 2) for ASCII