Goodrive20-EU series VFD    Fault tracking 
110 
The keypad is not in good 
connection or offline; 
The keypad cable is too long 
and there is strong interference; 
Part of the communication 
circuits of the keypad or main 
board have fault 
Check  the  environment  and 
eliminate  the  interference 
source; 
Replace  the hardware and ask 
for maintenance service; 
Change  hardware  and  ask  for 
maintenance service 
The keypad is not in good 
connection or offline; 
The keypad cable is too long 
and there is strong interference; 
Data storage error in keypad 
Check  the  environment  and 
eliminate  the  interference 
source; 
Replace  the hardware and ask 
for maintenance service; 
Backup  data  in  the  keypad 
again 
Grounding 
shortcut fault 1 
The output of the VFD is short 
circuited to the ground; 
There is fault in the current 
detection circuit; 
There is a great difference 
between the actual motor power 
setting and the VFD power 
Check if the connection of the 
motor is normal or not; 
Replace the hall; 
Replace the main control panel; 
Reset motor parameters and 
ensure those parameters are 
correct; 
Check whether motor power 
parameters in P2 group are 
consistent with the motor power 
actually used 
Grounding 
shortcut fault 2 
Electronic 
underload fault   
The VFD will report the 
underload pre-alarm according 
to the set value.   
Check the load and the 
underload pre-alarm point.   
STO function operates normally 
Fault or internal hardware circuit 
fault occurred to H1 channel 
Replace STO switch; if problem 
persists after replacement, 
contact the manufacturer. 
Fault or internal hardware circuit 
fault occurred to H2 channel 
Internal circuit 
abnormal 
Fault or internal hardware circuit 
fault occurred to H1 and H2 
channels simultaneously