GD200A series VFD Function parameters
-98-
Function
code
Name
Description
Default
value
Modify
Output frequency
of the motor
=the upper
frequency ?
Aauxiliary motor start ,
begin delay counting
Y
Reach the
start delay
time
Start the auxiliary
motor 1 and 2
=the lower
frequency ?
N Y
Aauxiliary motor stop ,
begin delay counting
Reach the
stop delay
time
Stop the auxiliary
motor 1 and 2
Y
Y
End
N
N
N
P24.10 is used to select the valid auxiliary motor.
0: No auxiliary motor
1: Auxiliary motor 1 valid
2: Auxiliary motor 2 valid
3: Auxiliary motor 1 and 2 valid
Setting range of P24.11: 0.03600.0s
Setting range of P24.12: 0.03600.0s