GD200A series VFD Function parameters
-88-
Function
code
Name
Description
Default
value
Modify
P10.37
Multi-step time
unit
0: Seconds; the running time of all steps is
counted by second
1: Minutes; the running time of all steps is counted
by minute
0
P11 Group Protective parameters
Function
code
Name
Description
Default
value
Modify
P11.00
Phase loss
protection
0x000x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Output phase loss protection disable
1: Output phase loss protection enable
LED hundreds:
0: Input phase loss hardware protection disable
1: Input phase loss hardware protection enable
111
P11.01
Sudden power
loss frequency
decrease
0: Disable
1: Enable
0
P11.02
Frequency
decrease ratio
of sudden
power loss
Setting range: 0.00Hz/sP00.03 (max. frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point,
the VFD begin to decrease the running frequency
at P11.02, to make the VFD generate power
again. The returning power can maintain the bus
voltage to ensure a rated running of the VFD until
power recovery.
Voltage degree
220V
380V
660V
Frequency decrease point
at sudden power loss
260V
460V
800V
Note:
1. Adjust the parameter properly to avoid the
stopping caused by VFD protection during the
switching of the grid.
2. Disable input phase loss protection to enable
this function.
10.00
Hz/s