EasyManuals Logo

INVT GD200A-0R7G-4 User Manual

INVT GD200A-0R7G-4
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
GD200A series VFD Function parameters
-79-
Function
code
Name
Description
Default
value
Modify
potentiometer integral function
0: The integral function is valid
1: The integral function is invalid
P08.43
Integral ratio of
the keypad
potentiometer
0.0110.00s
0.10s
P08.44
UP/DOWN
terminals
control
0x000x221
LED ones: frequency control selection
0: UP/DOWN terminals setting valid
1: UP/DOWN terminals setting valid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: All frequency means are valid
2: When the multi-step are priority, it is invalid to
the multi-step
LED hundreds: action selection when stop
0: Setting valid
1: Valid in the running, clear after stop
2: Valid in the running, clear after receiving the
stop commands
0x000
P08.45
UP terminals
frequency
incremental
change rate
0.0150.00Hz/s
0.50
Hz/s
P08.46
DOWN
terminals
frequency
incremental
change rate
0.0150.00 Hz/s
0.50
Hz/s
P08.47
Action when
the frequency
setting is off
0x0000x111
LED ones: Action selection when power off.
0: Save when power off
1: Clear when power off
LED tens: Action selection when MODBUS set
frequency off
0: Save when power off
1: Clear when power off
LED hundreds: The action selection when other
frequency set frequency off
0x000