Goodrive300 Series VFD    Communication protocol 
221 
-300.0–300.0% (unit: 0.1%) 
Identifying code 
of the VFD 
R/W  characteristics  means  the  function  is  with  read  and  write  characteristics.  For  example, 
"communication control command" is writing chrematistics and control the VFD with writing command 
(06H). R characteristic can only read other than write and W characteristic can only write other than 
read.   
Note: when operate on the VFD with the table above, it is necessary to enable some parameters. For 
example,  the  operation  of  running  and  stopping,  it  is  necessary  to  set  P00.01  to  communication 
running command channel and set P00.02 to Modbus communication channel. And when operate on 
"PID given", it is necessary to set P09.00 to "Modbus communication setting". 
The encoding rules for device codes (corresponds to identifying code 2103H of the VFD) 
10.4.6   Fieldbus ratio values 
The communication data is expressed by hex in actual application and there is no radix point in hex. 
For example, 50.12Hz cannot be expressed by hex so 50.12 can be magnified by 100 times into 5012, 
so hex 1394H can be used to express 50.12. 
A non-integer can be timed by a multiple to get an integer and the integer can be called fieldbus ratio 
values.   
The fieldbus ratio values are refered to the radix point of the setting  range or default value in the 
function parameter list. If there are figures behind the radix point (n=1), then the fieldbus ratio value m 
is
. Take the table as the example: