Goodrive300 Series VFD    Installation guide 
28 
P1 and (+) are connected with the terminals of the 
DC reactor.   
(+) and (-) are connected with the terminals of the 
braking unit. 
PB  and  (+)  are  connected  with  the  terminals  of 
the braking resistor.   
DC reactor terminal 
2, braking unit 
terminal 1 
380V/500V/660V: the grounding 
resistor is less than 10 Ohm   
 
Protective grounding terminals. Every machine is 
provided  with  2  PE  terminals  as  the  standard 
configuration. These terminals must be grounded 
with proper techniques. 
Control power supply terminal   
Optional parts for 380V VFDs, standard parts for 
660V VFDs (connected with external 220V control 
power supply), enabling a VFD to use an auxiliary 
power  supply  when  no  power  is  applied  in  the 
input  main  circuit,  thus  facilitating  the 
commissioning of the VFD and  improving safety 
during the commissioning. 
Note:   
•  Do  not use  an  asymmetrically constructed  motor cable.  If  there  is  a  symmetrically  constructed 
grounding conductor in the motor cable in addition to the conductive shield, connect the grounding 
conductor to the grounding terminal at the VFD and motor ends. 
•  Braking resistor, braking unit and DC reactor are optional parts.   
•  Route the motor cable, input power cable and control cables separately. 
•  If the terminal description is "/", the machine does not provide the terminal as the external terminal.   
4.3.3 Main circuit terminal wiring 
1.  Connect the ground line of input power cable to the ground terminal of VFD (PE) directly, and 
connect 3PH input cable to R, S and T and fasten up. 
2.  Connect the ground line of motor cable to the ground terminal of the VFD, and connect the 3PH 
motor cable to U, V, W and fasten up. 
3.  Connect the brake resistor which carries cables to the designated position.