Goodrive300 Series VFD    Communication protocol 
222 
Name
Function 
code
Description
Setting
range
Default
value
Modify
Serial
No.
P01.21
Hibernation
restore
delay time
Restart after
power off
0.0–3600.0s (valid when 
P01.19=2)
0: Disable
1: Enable
0.0–3600.0
0–1
0.0s
0
39.
40.
P01.20
 
If there is one figure behind the radix point in the setting range or the default value, then the fieldbus 
ratio value is 10. if the data received by the upper monitor is 50, then the "hibernation restore delay 
time" is 5.0 (5.0=50÷10). 
If Modbus communication is used to control the hibernation restore delay time as 5.0s. Firstly, 5.0 can 
be magnified by 10 times to integer 50 (32H) and then this data can be sent.   
VFD
address
Read
command
 
Parameters
address
 
Data number  CRC check 
01 06 01 14 00 32 49 E7
 
After the VFD receives the command, it will change 50 into 5 according to the fieldbus ratio value and 
then set the hibernation restore delay time as 5s. 
Another  example,  after  the  upper  monitor  sends  the  command  of  reading  the  parameter  of 
hibernation restore delay time ,if the response message of the VFD is as following:   
VFD
address
Read
command
 
Parameters
data
 
CRC check
 
2-byte
data
01 03 02 00 32 39 91
 
Because the parameter data is 0032H (50) and 50 divided by 10 is 5, then the hibernation restore 
delay time is 5s. 
10.4.7   Fault message response   
There may be fault in the communication control. For example, some parameter can only be read. If a 
writing message is sent, the VFD will return a fault response message.   
The fault message is from the VFD to the master, its code and meaning is as below:   
The  command  from  master  cannot  be  executed.  The  reason 
maybe: 
1. This command is only for new device; 
2. Slave is in fault state and cannot execute it. 
Some  of  the  operation  addresses  are  invalid  or  not  allowed  to 
access.  Especially  the  combination  of  the  register  and  the